Table Of Contents
Technical Specifications
Switch Specifications
Module Specifications
Weight of Modules
Power Specifications for the Cisco MDS 9513 Director
Specifications for the Cisco MDS 9513 Power Supplies
Component Power Requirements and Heat Dissipation for the Cisco MDS 9513 Director
AC Power Consumption for the Cisco MDS 9513 Director
Power Specifications for the Cisco MDS 9509 Director
Specifications for the Cisco MDS 9509 Power Supplies
Component Power Requirements and Heat Dissipation for the Cisco MDS 9509 Director
AC Power Consumption for the Cisco MDS 9509 Director
Power Specifications for the Cisco MDS 9506 Director
Specifications for the Cisco MDS 9506 Power Supplies
Component Power Requirements and Heat Dissipation for the Cisco MDS 9506 Director
AC Power Consumption for the Cisco MDS 9506 Director
X2 Transceiver Specifications
Cisco 10-Gbps Fibre Channel X2 Transceivers
General Specification for Cisco 10-Gbps Fibre Channel X2 Transceivers
Environmental Conditions and Power Requirement Specifications for Cisco 10-Gbps Fibre Channel X2 Transceivers
Cisco 10-Gbps Ethernet X2 Transceivers
General Specification for Cisco 10-Gbps Ethernet X2 Transceivers
Environmental and Power Requirements Specifications for Cisco 10-Gbps Ethernet X2 Transceiver
SFP Transceiver Specifications
Cisco Fibre Channel SFP Transceivers
General Specifications for Cisco 4-Gbps Fibre Channel SFP Transceivers
Environmental and Power Requirement for Cisco 4-Gbps Fibre Channel SFP Transceivers
General Specifications for Cisco 2-Gbps Fibre Channel SFP Transceivers
Environmental and Power Requirement for Cisco 2-Gbps Fibre Channel SFP Transceivers
Maximum Environmental and Electrical Ratings for Cisco Fibre Channel SFP Transceivers
Cisco Fibre Channel and Gigabit Ethernet Transceivers
General Specifications for Cisco Fibre Channel and Gigabit Ethernet SFP Transceivers
Environmental and Power Requirement Specifications for Cisco Fibre Channel and Gigabit Ethernet SFP Transceivers
Cisco CWDM SFP Transceivers
Environmental and Optical Specifications for Cisco 2-Gbps CWDM SFP Transceivers
Environmental and Optical Specifications for Cisco 4-Gbps CWDM SFP Transceivers
Cisco Gigabit Ethernet Transceivers
General Specifications for Cisco Gigabit Ethernet Transceivers
Environmental and Power Requirement Specifications for Cisco Gigabit Ethernet Transceivers
Technical Specifications
This appendix provides technical specifications and includes the following sections:
•
Switch Specifications
•
Module Specifications
•
Power Specifications for the Cisco MDS 9513 Director
•
Power Specifications for the Cisco MDS 9509 Director
•
Power Specifications for the Cisco MDS 9506 Director
•
X2 Transceiver Specifications
•
SFP Transceiver Specifications
Note
Specifications for cables and connectors are provided in Appendix C, "Cable and Port Specifications."
Switch Specifications
The Cisco MDS 9500 Series supports hot-swappable fan modules that provide 85 cfm (cubic feet per minute) of airflow per slot with 410 W of power dissipation per slot.
Table B-1 lists the environmental specifications for the Cisco MDS 9500 Series.
Table B-1 Environmental Specifications for the Cisco MDS 9500 Series
Description
|
Specification
|
Temperature, certified for operation
|
32 to 104°F (0 to 40°C)
|
Temperature, designed and tested for operation
|
32 to 130°F (0 to 55°C)
|
Temperature, ambient nonoperating and storage
|
-40 to 158°F (-40 to 70°C)
|
Humidity (RH), ambient (noncondensing) operating
|
10 to 90%
|
Humidity (RH), ambient (noncondensing) nonoperating and storage
|
5 to 95%
|
Altitude, certified for operation
|
0 to 6500 ft (0 to 2000 m)
|
Altitude, designed and tested for operation
|
-200 to 10000 ft (-60 to 3000 m)
|
Noise levels
|
70 dB
|
Table B-2 lists the physical specifications for the Cisco MDS 9513 Director.
Table B-2 Physical Specifications for the Cisco MDS 9513 Director
Description
|
Specification
|
Dimensions (HxWxD)
|
24.5 x 17.5 x 28 in. (62.2 x 44.5 x 71.1 cm) Chassis requires 14 RU1 , 15 RU with a rack-mount kit. Chassis depth including cable guide is 33 in. (83.8 cm).
Crossbar module: 1.7 x 14.0 x 11.2 in. (4.4 x 35.6 x 28.4 cm)
|
Weight
|
Chassis only: 101 lb (45.36 kg) Fully loaded chassis2 : 375 lb (170.10 kg)
System fan tray: 18 lbs (8.2 kg)
Crossbar module fan tray: 2.25 lbs (1.02 kg)
|
Power supply
|
6000-W, AC input 33 lb (15 kg)
|
Airflow
|
275 to 325 lfm3 through system fan module, or 90 cfm4 per supervisor, switching, or services module. Total of 1150 cfm if all slots are filled.
Spacing requirements:
• If installed in an open rack (no side panels), the horizontal distance required between the chassis and any devices that exhaust air towards the chassis is a minimum of 12 in. (304 cm), and the distance required between the chassis air vents and any walls is a minimum of 6 in. (15.2 cm).
|
Table B-3 lists the physical specifications for the Cisco MDS 9509 Director.
Table B-3 Physical Specifications for the Cisco MDS 9509 Director
Description
|
Specification
|
Dimensions (HxWxD)
|
24.5 x 17.25 x 18.8 in. (62.2 x 43.8 x 47.8 cm) Chassis requires 14 RU1 plus space for shelf brackets. Chassis depth including cable guide is 21.64 in. (55.0 cm).
|
Weight
|
Chassis only: 55 lb (24.9 kg) Chassis configured with two supervisor modules, and 2500-W power supplies: 120 lb (54.4 kg) Chassis configured with two supervisor modules, and 4000-W power supplies: 140 lb (63.5 kg)
System fan tray: 10.5 lb (5.0 kg).
|
Power supply
|
4000-W, AC input 3000-W, AC input 2500-W, AC input 2500-W, DC input
|
Airflow
|
300 lfm2 through system fan module, or 80 cfm3 per supervisor, switching, or services module. Total of 720 cfm if all slots are filled.
Spacing requirements:
• If installed in a cabinet, a minimum clearance of 2.5 in. (6.4 cm) is required between the chassis air vents and the cabinet walls.
• If installed in an open rack (no side panels), the horizontal distance required between the chassis and any devices that exhaust air towards the chassis is a minimum of 6 in. (15.2 cm), and the distance required between the chassis air vents and any walls is a minimum of 2.5 in. (6.4 cm).
|
Table B-4 lists the physical specifications for the Cisco MDS 9506 Director.
Table B-4 Physical Specifications for the Cisco MDS 9506 Director
Description
|
Specification
|
Dimensions (HxWxD)
|
12.25 x 17.37 x 21.75 in. (31.1 x 44.1 x 55.2 cm). Chassis requires 7 RU1 . Chassis depth including cable guides is 26.75 inches (67.9 cm).
|
Weight
|
Chassis only: 46 lb (20.9 kg). Chassis configured with two supervisor modules, fan module, and two power supplies: 86 lb (39 kg). System fan tray: 7.70 lbs (3.49 kg) 1900W AC power supply: 11 lbs (4.99 kg)
|
Power supply
|
1900-W, AC input 1900-W, DC input
|
Airflow
|
300 lfm2 through system fan module, or 80 cfm3 per supervisor, switching, or services module (total of 480 cfm if all slots are filled). Spacing requirements:
• If installed in a cabinet, a minimum of 2.5 in. (6.4 cm) is required between the chassis air vents and the cabinet walls.
• If installed in an open rack (no side panels), the horizontal distance required between the chassis and any devices that exhaust air towards the chassis is a minimum of 6 in. (15.2 cm), and the distance required between the chassis air vents and any walls is a minimum of 2.5 in. (6.4 cm).
|
Module Specifications
Table B-5 lists the specifications for the Cisco MDS 9500 Series supervisor modules, services modules, and switching modules.
Table B-5 Cisco MDS 9500 Series Module Specifications
Description
|
Specification
|
Environmental Requirements
|
Temperature, certified for operation
|
32 to 104°F (0 to 40°C)
|
Temperature, designed and tested for operation
|
32 to 130°F (0 to 55°C)
|
Temperature, ambient nonoperating and storage
|
-40 to 167°F (-40 to 75°C)
|
Humidity (RH), ambient (noncondensing) operating
|
10 to 90%
|
Altitude, certified for operation
|
0 to 6500 ft (0 to 2000 m)
|
Altitude, designed and tested for operation
|
-200 to 10000 ft (-60 to 3000 m)
|
Physical Characteristics
|
Dimensions
|
1.75 x15.5 x16.5 in. (4.4 x 39.4 x 41.9 cm)
Note These are the maximum dimensions of the faceplate and board, and include the connectors on the board.
|
Weight
|
8 to 11.5 lb (1.4 to 5.2 kg)
|
Weight of Modules
Table B-6 lists the weight for each module in the Cisco MDS 9000 Family.
Table B-6 Weight of Modules in the Cisco MDS 9000 Family
Module
|
Weight
|
Crossbar switching module
|
6 lb (2.7 kg)
|
48-port 4-Gbps switching module
|
11.0 lb (4.99 kg)
|
24-port 4-Gbps switching module
|
7.75 lb (3.52 kg)
|
12-port 4-Gbps switching module
|
7.5 lb (3.40 kg)
|
4-Port 10-Gbps switching module
|
8.5 lb (3.86 kg)
|
32-port FC switching module
|
9 lb (4.1 kg)
|
16-port FC switching module
|
9 lb (4.1 kg)
|
SSM
|
11 lb (5 kg)
|
ASM
|
11 lb (5 kg)
|
CSM
|
11.5 lb (5.2 kg)
|
IPS-8
|
10 lb (4.5 kg)
|
IPS-4
|
9 lb (4.1 kg)
|
MSM-18/4
|
8.5 lb (3.86 kg)
|
MSFM-18/4
|
8.5 lb (3.86 kg)
|
MPS-14/2
|
10 lb (4.5 kg)
|
Supervisor-2 for MDS 9500 Series
|
7.25 lb (kg)
|
Supervisor-1 for MDS 9500 Series
|
9 lb (4.1 kg)
|
Supervisor for MDS 9200 Series
|
9 lb (4.1 kg)
|
Crossbar module fan tray
|
2.25 lb (1.13 kg)
|
Module blank panels
|
0.50 lb (0.25 kg)
|
Table B-7 lists the specifications for the batteries on the Cisco MDS 9000 Family caching services module.
Note
The CSM does not support Cisco SAN-OS Release 3.0(1).
Table B-7 Caching Services Module Battery Specifications
Attribute
|
Value
|
Nominal voltage
|
9.6 V
|
Rated capacity
|
Typical discharge capacity at 0.2C rate: 2100 mAh
|
Minimum discharge capacity at 0.2C rate: 2000 mAh
|
Minimum discharge capacity at 5C rate: 1800 mAh (1 V/cell discharge cut-off)
|
Discharge
|
The battery is capable of continuous discharge from 41 to 140°F (5 to 60°C) at 5C-rate
|
Charge
|
From 32 to 59°F (0 to 15°C) at C/10 rate and from 59 to 104°F (15 to 40°C) at C/2 rate
|
Storage temperature
|
32 to 95°F (0 to +35°C)
|
Relative humidity range
|
From 5 to 90%
|
Power Specifications for the Cisco MDS 9513 Director
This section includes the following topics:
•
Specifications for the Cisco MDS 9513 Power Supplies
•
Component Power Requirements and Heat Dissipation for the Cisco MDS 9513 Director
•
AC Power Consumption for the Cisco MDS 9513 Director
Specifications for the Cisco MDS 9513 Power Supplies
The 6000-W AC power supply provides power based upon the input voltage. Each power supply has two AC power connections and will provide power as follows:
•
One AC power connection @110 VAC = No output
•
Two AC power connection @110 VAC = 2900 W output
•
One AC power connection @ 220 VAC = 2900 W output
•
One AC power connection @110 VAC and one AC power connection @ 220 VAC = 2900 W output
•
Two AC power connection @ 220 VAC = 6000 W output
If a 110 VAC input is chosen, a 110-VAC power cord (CAB-7513AC=) must be ordered separately.
Note
Power output does not include the power used by the individual modules used in the chassis.
Table B-8 lists the specifications for the Cisco MDS 9513 power supplies.
Table B-8 Specifications for Cisco MDS 9513 Power Supplies
Description
|
Specification
|
6000-W AC Power Supply
|
Type
|
Autoranging input with power factor corrector.
|
Voltage
|
100 to 240 VAC (±10%).
|
Current rating
|
16 A maximum at 100 to 120 VAC and 2900-W output. 16 A maximum at 200 to 240 VAC and 6000-W output.
|
Frequency
|
50 to 60 Hz (nominal) (±3 Hz for full range).
|
Output capacity
|
One AC power connection @110 VAC = No output
Two AC power connection @110 VAC = 2900 W output
One AC power connection @ 220 VAC = 2900 W output
One AC power connection @110 VAC and one AC power connection @ 220 VAC = 2900 W output
Two AC power connection @ 220 VAC = 6000 W output
|
Output voltage at 110/120
|
3.3 V at 10 A, 50 V at 57 A
|
Output voltage at 200/240
|
3.3 V at 10A, 50 V at 119 A
|
Component Power Requirements and Heat Dissipation for the Cisco MDS 9513 Director
Consider heat dissipation when sizing the air-conditioning requirements for an installation. The power and heat associated with a Cisco MDS 9513 Director varies based upon the following considerations:
•
Power supply type
•
Switching module type and number of switching modules installed
•
Average switching traffic levels
Table B-9 lists the power requirements and heat dissipation for the components of the Cisco MDS 9513 Director.
Note
Unless noted otherwise, the data listed in Table B-9 is based on worst-case conditions. Typical numbers are approximately 30 percent below the numbers listed here.
Table B-9 Requirements and Heat Dissipation for 6000-W AC Power Supplies
Module Type/ Product Number
|
SAN-OS Release
|
Power Required (watts)
|
Heat Dissipation (BTU/hr)
|
Input Current
|
90 VAC (amps)
|
120 VAC (amps)
|
180 VAC (amps)
|
240 VAC (amps)
|
Fan tray 1 (front panel), DS-13SLT-FAN-F
|
3.x
|
248
|
1059
|
3.44
|
2.58
|
1.72
|
1.29
|
Fan tray 2 (rear panel), DS-13SLT-FAN-R
|
3.x
|
70
|
299
|
0.97
|
0.73
|
0.49
|
0.36
|
Cisco MDS 9513 chassis, DS-C9513, with front (DS-13SLT-FAN-F) and rear (DS-13SLT-FAN-R) fan trays
|
3.x
|
318
|
1358
|
4.41
|
3.31
|
2.21
|
1.65
|
Supervisor-2, DS-X9530-SF2-K9
|
3.x
|
126
|
538
|
1.75
|
1.31
|
0.88
|
0.66
|
48-port 4-Gbps switching module, DS-X9148
|
3.x
|
185
|
790
|
2.57
|
1.93
|
1.28
|
0.96
|
24-port 4-Gbps switching module, DS-X9124
|
3.x
|
147
|
628
|
2.04
|
1.53
|
1.02
|
0.77
|
12-port 4-Gbps switching module, DS-X9112
|
3.x
|
132
|
564
|
1.83
|
1.38
|
0.92
|
0.69
|
4-Port 10-Gbps switching module, DS-X9704
|
3.x
|
172
|
734
|
2.39
|
1.79
|
1.19
|
0.90
|
18/4 Multiservice module, DS-X9304-18K9
|
3.2.(1)
|
200
|
855
|
2.78
|
2.08
|
1.39
|
1.04
|
Crossbar module, DS-13SLT-FAB1, DS-13SLT-FAB2
|
3.x
|
63
|
269
|
0.88
|
0.66
|
0.44
|
0.33
|
AC Power Consumption for the Cisco MDS 9513 Director
Table B-10 shows the typical AC power consumption for a Cisco MDS 9513 Director.
Table B-10 Typical AC Power Consumption for a Cisco MDS 9513 Director
Module Type / Product Number
|
Typical AC Power Consumption (Watts)
|
Cisco MDS 9513 chassis, DS-C9513, with front (DS-13SLT-FAN-F) and rear (DS-13SLT-FAN-R) fan trays, two Supervisor-2 (DS-X9530-SF2-K9), and two crossbar modules (DS-13SLT-FAB1 or DS-13SLT-FAB2)
|
697
|
48-port 4-Gbps switching module, DS-X9148
|
181
|
24-port 4-Gbps switching module, DS-X9124
|
127
|
12-port 4-Gbps switching module, DS-X9112
|
107
|
4-Port 10-Gbps switching module, DS-X9704
|
162
|
Power Specifications for the Cisco MDS 9509 Director
This section includes the following topics:
•
Specifications for the Cisco MDS 9509 Power Supplies
•
Component Power Requirements and Heat Dissipation for the Cisco MDS 9509 Director
•
AC Power Consumption for the Cisco MDS 9509 Director
Specifications for the Cisco MDS 9509 Power Supplies
The 3000-W AC power supply provides power based upon the input voltage, as follows:
•
Maximum of 1400 W at input of 100 to 120 VAC (1174 W available to modules and fans)
•
Maximum of 3000 W at input of 200 to 240 VAC (2774 W available to modules and fans)
The 2500-W AC power supply provides power based upon the input voltage, as follows:
•
Maximum of 1325 W at input of 100 to 120 VAC (1150 W available to modules and fans)
•
Maximum of 2525 W at input of 200 to 240 VAC (2331 W available to modules and fans)
If a 110-VAC input is chosen, a 110-VAC power cord (CAB-7513AC=) must be ordered separately.
Table B-11 lists the specifications for the Cisco MDS 9509 power supplies.
Table B-11 Specifications for Cisco MDS 9509 Power Supplies
Description
|
Specification
|
2500-W AC Power Supply
|
Type
|
Autoranging input with power factor corrector.
|
Voltage
|
100 to 240 VAC (±10%).
|
Current rating
|
16 A maximum at 100 to 120 VAC and 1300-W output. 16 A maximum at 200 to 240 VAC and 2500-W output.
Note For current ratings of plugs, see Figure C-5 on page C-10.
|
Frequency
|
50 to 60 Hz (nominal) (±3 Hz for full range).
|
Output capacity
|
1325 W maximum (100 to 120 VAC). 2525 W maximum (200 to 240 VAC).
|
Output voltage at 110/120
|
3.3 V at 15 A; 5 V at 5 A; 12 V at 12 A; 42 V at 27.5 A.
|
Output voltage at 200/240
|
3.3 V at 1 5 A; 5 V at 5 A; 12 V at 12 A; 42 V at 55.5 A.
|
2500-W DC Power Supply
|
Voltage
|
-48 VDC to -60 VDC continuous.
|
Current rating
|
70 A at -48 VDC; 55 A at -60 VDC; 80 A at -40.5 VDC.
|
Terminal block
|
Accommodates 2 to 14 AWG copper conductors. Use 90°C copper conductors for North American installations.
Note Actual size of the wire required is determined by the installer or local electrician. Terminal block material is rated at 302°F (150°C).
|
Output capacity
|
2525 W maximum (-48 to -60 VDC).
|
Output voltage
|
3.3 V at 15 A; 5 V at 5 A; 12 V at 12 A; 42 V at 55.5 A.
|
3000-W AC Power Supply
|
Type
|
Autoranging input with power factor corrector.
|
Voltage
|
100 to 240 VAC (±10%).
|
Current rating
|
17.6 A maximum at 100 to 120 VAC and 1400-W output. 17.6 A maximum at 200 to 240 VAC and 3000-W output.
For current ratings of plugs, see Figure C-5 on page C-10
|
Frequency
|
50 to 60 Hz (nominal) (±3 Hz for full range).
|
Output capacity
|
1400 W maximum (100 to 120 VAC). 3000 W maximum (200 to 240 VAC).
|
Output voltage at 110/120
|
3.3 V at 15 A; 12 V at 12 A; 42 V at 27.9 A.
|
Output voltage at 200/240
|
3.3 V at 1 5 A; 12 V at 12 A; 42 V at 66 A.
|
4000-W AC Power Supply
|
Type
|
High-line input with power factor corrector, 220 VAC, single-phase circuit.
|
Voltage
|
200 to 240 VAC (±10%).
|
Current rating
|
23 A
Note For current ratings of plugs, see Figure C-8 on page C-12.
|
Frequency
|
50/60 Hz (nominal) (±3% for full range).
|
Output capacity
|
4000 W maximum.
|
Output voltage at 200/240
|
3.3 V at 15 A; 5 V at 5 A; 12 V at 12 A; 42 V at 91.2 A
|
Component Power Requirements and Heat Dissipation for the Cisco MDS 9509 Director
When sizing the air-conditioning requirements for an installation, consider heat dissipation. The power and heat associated with a Cisco MDS 9509 Director varies based upon the following considerations:
•
Power supply type
•
Switching module type and number of switching modules installed
•
Average switching traffic levels
Table B-12 and Table B-13 list the power requirements and heat dissipation for the components of the Cisco MDS 9509 Director.
Note
Unless noted otherwise, the data listed in Table B-12 and Table B-13 is based on worst-case conditions. Typical numbers are approximately 30 percent below the numbers listed here.
Table B-12 Requirements and Heat Dissipation for 2500-, 3000-, and 4000-W AC Power Supplies
Module Type/ Product Number
|
SAN-OS Release
|
Power Required (watts)
|
Heat Dissipation (BTU/hr)
|
Input Current
|
90 VAC (amps)
|
120 VAC (amps)
|
180 VAC (amps)
|
240 VAC (amps)
|
Cisco MDS 9509 chassis with fan module DS-C9509
|
3.x
|
210
|
897
|
2.92
|
2.19
|
1.46
|
1.09
|
2.x and 1.x
|
216
|
920
|
3.00
|
2.25
|
1.50
|
1.13
|
Supervisor/fabric 1 DS-X9530-SF1
|
3.x
|
210
|
897
|
2.92
|
2.19
|
1.46
|
1.09
|
2.x and 1.x
|
220
|
940
|
3.05
|
2.29
|
1.53
|
1.15
|
Supervisor-2, DS-X9530-SF2-K9
|
3.x
|
126
|
538
|
1.75
|
1.31
|
0.88
|
0.66
|
48-port 4-Gbps switching module, DS-X9148
|
3.x
|
185
|
790
|
2.57
|
1.93
|
1.28
|
0.96
|
2.x and 1.x
|
—
|
—
|
—
|
—
|
—
|
—
|
24-port 4-Gbps switching module, DS-X9124
|
3.x
|
147
|
628
|
2.04
|
1.53
|
1.02
|
0.77
|
2.x and 1.x
|
—
|
—
|
—
|
—
|
—
|
—
|
12-port 4-Gbps switching module, DS-X9112
|
3.x
|
132
|
564
|
1.83
|
1.38
|
0.92
|
0.69
|
2.x and 1.x
|
—
|
—
|
—
|
—
|
—
|
—
|
4-Port 10-Gbps switching module, DS-X9704
|
3.x
|
172
|
734
|
2.39
|
1.79
|
1.19
|
0.90
|
2.x and 1.x
|
—
|
—
|
—
|
—
|
—
|
—
|
32-port 1-Gbps/2-Gbps Fibre Channel module, DS-X9032
|
3.x
|
191
|
816
|
.2.65
|
1.99
|
1.33
|
0.99
|
2.x and 1.x
|
200
|
855
|
2.78
|
2.08
|
1.39
|
1.04
|
16-port 1-Gbps/2-Gbps Fibre Channel module, DS-X9016
|
3.x
|
210
|
897
|
2.92
|
2.19
|
1.46
|
1.09
|
2.x and 1.x
|
220
|
940
|
3.05
|
2.29
|
1.53
|
1.15
|
18/4 Multiservice module, DS-X9304-18K9
|
3.2.(1)
|
200
|
855
|
2.78
|
2.08
|
1.39
|
1.04
|
MPS-14/2 module DS-X9302-14K9
|
3.x
|
200
|
854
|
2.78
|
2.08
|
1.39
|
1.04
|
2.x and 1.x
|
227
|
970
|
3.15
|
2.37
|
1.57
|
1.19
|
8-port IPS module DS-X9308-SMIP
|
3.x
|
200
|
854
|
2.78
|
2.08
|
1.39
|
1.04
|
2.x and 1.x
|
220
|
940
|
3.05
|
2.29
|
1.53
|
1.15
|
4-port IPS module DS-X9304-SMIP
|
3.x
|
160
|
683
|
2.22
|
1.67
|
1.11
|
0.83
|
2.x and 1.x
|
185
|
789
|
2.57
|
1.93
|
1.28
|
0.96
|
32-port SSM DS-X9032-SSM
|
3.x
|
281
|
1200
|
3.90
|
2.93
|
1.95
|
1.46
|
2.x and 1.x
|
295
|
1260
|
4.10
|
3.07
|
2.05
|
1.54
|
32-port ASM DS-X9032-SMV
|
3.x
|
281
|
1200
|
3.90
|
2.93
|
1.95
|
1.46
|
2.x and 1.x
|
295
|
1260
|
4.10
|
3.07
|
2.05
|
1.54
|
CSM DS-X9560-SMC
|
3.x
|
200
|
854
|
2.78
|
2.08
|
1.39
|
1.04
|
2.x and 1.x
|
210
|
919
|
2.99
|
2.19
|
1.50
|
1.12
|
Table B-13 Power Requirements and Heat Dissipation for the 2500-W DC Power Supply
Module Type/ Product Number
|
SAN-OS Release
|
Power Required (watts)
|
Heat Dissipation (BTU/hr)
|
Input Current
|
48 VDC (amps)
|
60 VDC (amps)
|
Cisco MDS 9509 chassis with fan module DS-C9509
|
3.x
|
210
|
956
|
5.83
|
4.67
|
2.x and 1.x
|
216
|
983
|
6.00
|
4.80
|
Supervisor/fabric 1 DS-X9530-SF1
|
3.x
|
210
|
956
|
5.83
|
4.67
|
2.x and 1.x
|
220
|
1000
|
6.10
|
4.88
|
32-port 1-Gbps/2-Gbps Fibre Channel module DS-X9032
|
3.x
|
191
|
869
|
5.31
|
4.24
|
2.x and 1.x
|
200
|
911
|
5.56
|
4.45
|
16-port 1-Gbps/2-Gbps Fibre Channel module DS-X9016
|
3.x
|
210
|
956
|
5.83
|
4.67
|
2.x and 1.x
|
220
|
1000
|
6.10
|
4.88
|
MSM-18/4 module, DS-X9304-18K9
|
3.2(1)
|
200
|
855
|
2.78
|
2.08
|
MSFM-18/4 module, DS-X9304-18FK9
|
3.2(1)
|
200
|
855
|
2.78
|
2.08
|
MPS-14/2 module DS-X9302-14K9
|
3.x
|
200
|
910
|
5.56
|
4.44
|
2.x and 1.x
|
227
|
970
|
3.15
|
2.37
|
8-port IPS module DS-X9308-SMIP
|
3.x
|
200
|
910
|
5.56
|
4.44
|
2.x and 1.x
|
220
|
1000
|
6.10
|
4.88
|
4-port IPS module DS-X9304-SMIP
|
3.x
|
160
|
728
|
4.44
|
3.56
|
2.x and 1.x
|
185
|
841
|
5.14
|
4.11
|
32-port SSM DS-X9032-SSM
|
3.x
|
281
|
1279
|
7.81
|
6.24
|
2.x and 1.x
|
295
|
1342
|
8.19
|
6.56
|
32-port ASM DS-X9032-SMV
|
3.x
|
281
|
1279
|
7.81
|
6.24
|
2.x and 1.x
|
295
|
1342
|
8.19
|
6.56
|
CSM DS-X9560-SMC
|
3.x
|
200
|
910
|
5.56
|
4.44
|
2.x and 1.x
|
210
|
956
|
5.83
|
4.67
|
AC Power Consumption for the Cisco MDS 9509 Director
Table B-14 shows the typical AC power consumption for the Cisco MDS 9509 Director
Table B-14 Typical AC Power Consumption for a Cisco MDS 9509 Director
Module Type / Product Number
|
Typical AC Power Consumption (Watts)
|
Cisco MDS 9509 chassis, DS-C9509, with fan module, and two Supervisor-2 (DS-X9530-SF2-K9)
|
380
|
Cisco MDS 9509 chassis, DS-C9509, with fan module, and two Supervisor-1 (DS-X9530-SF1-K9)
|
622
|
48-port 4-Gbps switching module, DS-X9148
|
181
|
24-port 4-Gbps switching module, DS-X9124
|
127
|
12-port 4-Gbps switching module, DS-X9112
|
107
|
4-Port 10-Gbps switching module, DS-X9704
|
162
|
32-port 1-Gbps/2-Gbps Fibre Channel module, DS-X9032
|
174
|
16-port 1-Gbps/2-Gbps Fibre Channel module, DS-X9016
|
144
|
MPS-14/2 module, DS-X9302-14K9
|
178
|
32-port SSM, DS-X9032-SSM
|
211
|
8-port IPS module, DS-X9308-SMIP
|
175
|
4-port IPS module, DS-X9304-SMIP
|
128
|
Power Specifications for the Cisco MDS 9506 Director
This section includes the following topics:
•
Specifications for the Cisco MDS 9506 Power Supplies
•
Component Power Requirements and Heat Dissipation for the Cisco MDS 9506 Director
•
AC Power Consumption for the Cisco MDS 9506 Director
Specifications for the Cisco MDS 9506 Power Supplies
Caution 
The following applies to AC power supplies on the Cisco MDS 9506 only:
The DS-C9506 equipment is suitable for use on TN power systems and the IT-power system connection of Norway (max 230 v phase-phase). If connected to a 230/400-V IT power system, beware of high leakage current. Earth connection is essential before connecting the supply.
The 1900-W AC power supply provides power based upon the input voltage:
•
Maximum of 1050 W at input of 100 to 120 VAC
•
Maximum of 1900 W at input of 200 to 240 VAC
A 110-VAC power cord (CAB-7513AC=) must be ordered separately.
Table B-15 lists the specifications for the Cisco MDS 9506 power supplies.
Table B-15 Specifications for Cisco MDS 9506 Power Supplies
Description
|
Specification
|
1900-W AC Power Supply
|
Type
|
Autoranging input with power factor corrector.
|
Voltage
|
100 to 240 VAC (±10%).
|
Current rating
|
12 A maximum at 100 to 120 VAC and 1050-W output. 12 A maximum at 200 to 240 VAC and 1900-W output.
Note For current ratings of plugs, see Figure C-5 on page C-10.
|
Frequency
|
50/60 Hz (nominal) (±3 Hz for full range).
|
Output capacity
|
1050 W maximum (at input of 100 to 120 VAC). 1900 W maximum (at input of 200 to 240 VAC).
|
Output voltage at 110/120
|
3.3 V at 2.5 A; 1.5 V at 15 A; 50 V at 20.4 A.
|
Output voltage at 200/240
|
3.3 V at 2.5 A; 1.5 V at 15 A; 50 V at 37.4 A.
|
1900-W DC Power Supply
|
Voltage
|
-48 to -60 VDC continuous.
|
Current rating
|
50 A at -48 VDC, 40 A at -60 VDC, 60 A at -40.5 VDC.
|
Terminal block
|
Accommodates 2 to 14 AWG copper conductors. Use 90°C copper conductors for North American installations.
Note Actual size of the wire required is determined by the installer or local electrician. Terminal block material is rated at 302°F (150°C).
|
Output capacity
|
1900 W maximum (at input of -48 to -60 VDC).
|
Output voltage
|
3.3 V at 2.5 A; 1.5 V at 15 A; 50 V at 37.4 A.
|
Component Power Requirements and Heat Dissipation for the Cisco MDS 9506 Director
When sizing the air-conditioning requirements for an installation, consider heat dissipation. The power and heat associated with a Cisco MDS 9506 Director varies depending upon the following:
•
Power supply type
•
Switching module type and number of switching modules installed
•
Average switching traffic levels
Table B-16 and Table B-16 list the AC and DC power requirements and heat dissipation for the components of the Cisco MDS 9506 Director.
Note
Unless noted otherwise, the information listed in Table B-16 and Table B-16 is based on worst-case conditions. Typical numbers are approximately 30 percent below the numbers listed here.
Table B-16 Power Requirements and Heat Dissipation for the 1900-W AC Power Supply
Module Type/ Product Number
|
SAN-OS Release
|
Power Required (watts)
|
Heat Dissipation (BTU/hr)
|
Input Current
|
90 VAC (amps)
|
120 VAC (amps)
|
180 VAC (amps)
|
240 VAC (amps)
|
Cisco MDS 9506 chassis with fan module DS-C9506
|
3.x
|
126
|
538
|
1.75
|
1.31
|
0.88
|
0.66
|
2.x and 1.x
|
126
|
538
|
1.75
|
1.32
|
0.88
|
0.66
|
Supervisor/fabric 1 DS-X9530-SF1
|
3.x
|
210
|
897
|
2.92
|
2.19
|
1.46
|
1.09
|
2.x and 1.x
|
220
|
940
|
3.05
|
2.29
|
1.53
|
1.15
|
Supervisor-2, DS-X9530-SF2-K9
|
3.x
|
126
|
538
|
1.75
|
1.31
|
0.88
|
0.66
|
48-port 4-Gbps switching module, DS-X9148
|
3.x
|
185
|
790
|
2.57
|
1.93
|
1.28
|
0.96
|
2.x and 1.x
|
—
|
—
|
—
|
—
|
—
|
—
|
24-port 4-Gbps switching module, DS-X9124
|
3.x
|
147
|
628
|
2.04
|
1.53
|
1.02
|
0.77
|
2.x and 1.x
|
—
|
—
|
—
|
—
|
—
|
—
|
12-port 4-Gbps switching module, DS-X9112
|
3.x
|
132
|
564
|
1.83
|
1.38
|
0.92
|
0.69
|
2.x and 1.x
|
—
|
—
|
—
|
—
|
—
|
—
|
4-Port 10-Gbps switching module, DS-X9704
|
3.x
|
172
|
734
|
2.39
|
1.79
|
1.19
|
0.90
|
2.x and 1.x
|
—
|
—
|
—
|
—
|
—
|
—
|
32-port 1-Gbps/2-Gbps Fibre Channel module DS-X9032
|
3.x
|
191
|
816
|
2.65
|
1.99
|
1.33
|
0.99
|
2.x and 1.x
|
200
|
855
|
2.78
|
2.08
|
1.39
|
1.04
|
16-port 1-Gbps/2-Gbps Fibre Channel module DS-X9016
|
3.x
|
210
|
897
|
2.92
|
2.19
|
1.46
|
1.09
|
2.x and 1.x
|
220
|
940
|
3.05
|
2.29
|
1.53
|
1.15
|
18/4 Multiservice module, DS-X9304-18K9
|
3.2.(1)
|
200
|
855
|
2.78
|
2.08
|
1.39
|
1.04
|
MPS-14/2 module DS-X9302-14K9
|
3.x
|
200
|
854
|
2.78
|
2.08
|
1.39
|
1.04
|
2.x and 1.x
|
227
|
970
|
3.15
|
2.37
|
1.57
|
1.19
|
8-port IPS module DS-X9308-SMIP
|
3.x
|
200
|
854
|